22 AWG (7 x 30) Tinned copper, Pe insulated 1 Twisted pair , Beldfoil Aluminium-Polyester Shield with Z-fold, 22 AWG (7 x 30) tinned copper drainwire and Low Smoke No Halogen jacket
Cable Construction
Nominal Insulation Thickness: | 0.38mm |
Nominal Diameter over Insulation: | 1.57mm |
Twisted Pair Lay Length: | 40mm |
Nominal Jacket Thickness: | 0.89mm |
Nominal Outer Diameter: | 4.9mm |
Insulation material: | Pe |
Sheath Material: | Low Smoke No Halogen (LSNH) |
Sheath Colour: | Chrome RAL 7037 |
Shield: | 100% Aluminium Polyester |
Mechanical Properties
Temperature Rating: | -15 to +80°C |
Maximum Pulling Tension: | 150N |
Minimum Bend Radius: | 45mm |
Applicable Specifications: | BS 7655 Section 6.1 Table 1 LTS 3 |
Flame Resistance: | IEC 332-3-C |
Electrical Properties
Maximum operating voltage: | 300V Rms |
Maximum Continuous current per conductor at 25°C: | 2.9 A |
Nominal Capacitance between conductors of a pair @ 1kHz: | 79nF/km |
Nominal capacitance conductor to shield @ 1 kHz: | 154 nF/km |
Nom. Conductor DC resistance @ 20°C: | 57.4 Ohm/km |
Nom. Shield DC resistance @ 20°C: | 50 Ohm/km |
Velocity of propagation: | 66% |