This cable is suitable for frequency converter controlled drives in the mining and tunneling industry.
Cable Construction
Conductor: | Flexible tinned copper conductor Cl. 5, acc to IEC 60228, DIN VDE 0295 |
Insulation: | rubber EPR type 3G13 acc. to DIN VDE 0207 |
Colour cores: | 3 conductors + 3 earth conductors: divided in 3 inetrstices |
Stranding: | power cores and protective earth conductors |
Inner sheath: | EPR compound Gm1b acc. to DIN VDE 0207, part 21 |
Outer sheath: | yellow, PCP compound 5GM5 |
Technical Details
Temperature range: | |
Fixed installation: | – 40°C + 80°C |
Flexible installation: | – 25°C + 80°C |
Temperature on conductor: | |
In service: | + 90°C |
In short circuit: | + 250°C |
Nominal voltage: | Uo/U 0,6/1 kV |
Test voltage: | 3000 V |
Max. operating voltage: | A.C. Uo/U = 0,7/1,2 kVD.C. Uo/U = 0,9/1,8 kV |
Tensile strength static: | 15 N/mm2 |
Fire resistance: | VDE 0482, part 332-1-2, EN/IEC 60332-1-2 |
Oil resistance: | DIN VDE 0473, part 811-2-1, EN/IEC 60811-2-1 |
Weather Resistance: | outdoor use and indoors,resistant to ozone, moisture and water |
Approvals: | GOST-R,WUG and other on request |
Ordering Information
No. of cores x cross section n x |
Outer-Ø ca. mm | Copper weight | Cable weight approx. | Tensile strength | AWG |
mm2 | ± 10% | kg/km | kg/km | N | no.*) |
3×16+3G2,5 | 26,2 | – | 1200 | 720 | 6 |
3×25+3G4 | 30 | – | 1700 | 1125 | 4 |
3×35+3G16/3 | 32,5 | – | 2200 | 1575 | 2 |
3×50+3G25/3 | 38 | – | 2800 | 2250 | 1 |
3×70+3G35/3 | 43 | – | 3850 | 3150 | 2/0 |
3×95+3G50/3 | 47,5 | – | 4650 | 4275 | 3/0 |
3×120+3×70/3 | 51 | – | 5800 | 5400 | 4/0 |
3×150+3×70/3 | 58 | – | 7150 | 6750 | 250 MCM |
3×185+3×95/3 | 62,5 | – | 8500 | 9200 | 350 MCM |
3×240+3×120/3 | 68,5 | – | 10100 | 11500 | 450 MCM |