Flexible single-core 76/132-138 kV acc. to DIN VDE 0250 part 813
Cable Features
- Small cable weight
- small outer diameter
- MSHA and WVG approvals on request
- possible cold version -50°C
- small bendding radius used
Cable Construction
Conductor: | Flexible tinned copper conductor Cl. 5,acc to IEC 60228, DIN VDE 0295 |
Conductor screen: | semi-conducting rubber compound |
Insulation: | rubber EPR special compound |
Core screen: | semi-conducting rubber compound |
Colour core: | natural color withblack semi-contuctive compound |
Screen: | spiral of tinned copper wires |
Outer sheath: | red, special rubber compound 5GM3acc. to DIN VDE 0207 part 21 |
Cable Technical Data
Temperature range | |
Fixed installation: | – 50°C + 80°C |
Flexible installation: | – 40°C + 80°C |
Temperature on conductor: | |
in service: | + 90°C |
in short-circuit: | + 250°C |
Temperature on screen: | |
in short-circuit | + 350°C |
Nominal voltage: | Uo/U 76/132-138 (145) kV |
Min. bending radius: | |
fixed installation: | 5 x d |
flexing installation: | 10 x d |
Tests: | acc. to DIN VDE 0250 part 813, IEC 60840 |
Cable Ordering Information
No. of cores x cross sectionn x mm2 | Outer-Ø ca. mm± 10% | Copper weightkg/km | Cable weight approx.kg/km |
Tensile strengthN | AWGno.*) |
1×240/105 | 70.7 | 7200 | – | 450 MCM |