Cable Application
A range of cables primarily designed for the interconnection of telephone equipment which is installed indoors. These cables may also be used for interconnection of other communication and control equipment or low level signalling applications.
Standards: CW1308 is available from 1 pair to 320 pairs. CW1308 is also available in LSHF.
Technical Information
Conductor: | Tinned/plain copper, 1/0.5mm |
Insulation: | PVC, insulated conductors twisted into pairs |
Pairs: | Laid up in concentric layers |
Core: | Covered with PET foil |
Screening: | Aluminium/PET screen with drain wire |
Outer sheath: | PVC with ripcord, white or black |
Maximum Conductor Resistance at 20oC: | 97.8 Ohm / km |
Minimum Insulation Resistance at 20oC: | 50 M ohm / km |
Maximum Capacitance Unbalance: | 500 pF/500m |
Minimum Bending Radius: | 15 x Ø |
Temperature Range during Operation: | -30oC to +70oC |
Temperature Range during Installation: | -5oC to +50oC |
Number of pairs | Conductor diameter | O/Dmm | Weight kg/km |
2 | 1/0.50 | 4.5 | 22 |
3 | 1/0.50 | 5 | 31 |
4 | 1/0.50 | 5.8 | 34 |
5 | 1/0.5 | 6.3 | 39 |
6 | 1/0.50 | 6.8 | 50 |
8 + E | 1/0.50 | 7.6 | 58 |
10 + E | 1/0.50 | 8.6 | 102 |
20 + E | 1/0.50 | 12 | 161 |
25 + E | 1/0.50 | 12.9 | 172 |
50 + E | 1/0.50 | 17 | 352 |
100 + E | 1/0.50 | 27 | 687 |
200 + E | 1/0.50 | 32 | 1,298 |
Click to download our Catalogue PDF for CW 1308 Cable.