Inverter, connection to frequency converters, UV Resistant, UL style 2277 WTTC 1000 V 90°C Dry 75°C Wet
Cable Construction
Conductor: | Flexible red copper conductor Cl. 5, acc to IEC 60228, DIN VDE 0295 |
Insulation: | PVC/Nylon special compound |
Cores colour: | 4 conductors: black conductors and green/yellow or 3 black conductors + 3 earth conductors |
Stranding: | in layers |
Screen: | 1 Aluminium tape + PETP foil + tinned copper drain wire 2 tinned copper braid |
Ripcord: | high strength ripcord under outer sheath |
Outer sheath: | black (RAL 9005), CPE special compound other colours on request |
Cable Features
- UV resistant
- outdoor use
- Installation in hazardous areas
- UL Type TC-ER c(UL) Type CIC FT4, Sun Res, Oil Res I
- UL style 1277 60°C 600 V WTTC and
- UL 1277, UL type TC-ER for 600 V on request
- UL style 2277 WTTC 1000 V 90°C dry
- tinned copper on request
- on request MSHA approved
Technical data
Nominal voltage: | UL: 1000 V |
Temperature range: | |
Fixed installation: | – 25°C to + 90°C |
Flexible application: | – 25°C to + 90°C |
Min. bending radius: | |
Fixed installation: | up to 12 mm: 10 x d > 12 to 20 mm: 15 x d > 20 mm: 20 x d |
Flexible installation: | up to 12 mm: 10 x d > 12 to 20 mm: 15 x d > 20 mm: 20 x d |
Resistance: | Fire performance: c(UL) FT4 Oil resistance: oil fuel CSA C22-2.NO.210-05 |
UL/CSA standards: | ASTM B-3 ASTM B-33 ASTM B-172 ASTM B-174 UL 66 basic construction, test and marking UL 83 600 V thermoplastic insulation UL 1277 60°C for Oil Res I CSA C22.2 No 230 for tray cable CSA C22.2 No 239 for control and instrumentation cable |
Ordering Information
Black 4 Conductors
No. of cores x cross section n x mm2 |
Outer Ø inches/mm ±10% |
Current capacity at +30°C Amps |
Copper weight Lbs/Mft – kg/km |
Cable weight approx. Lbs/Mft – kg/km |
AWG no.*) |
3×120+3G16 | 1.76 – 44.7 | 260 | – | 3139 – 4671 | 4/0 / 6 |
3×150+3G16 | 1.915 – 48.6 | 290 | – | 3596 – 53 51 | 250 MCM / 6 |
3×185+3G25 | 2.13 – 54.1 | 350 | – | 4873 – 7521 | 350 MCM / 6 |
3×240+3G35 | 2.26 – 57.3 | 430 | – | 6378 – 9520 | 450 MCM / 2 |
4 G 50 | 1.33- 33.8 | 145 | – | 1651 – 2457 | 1 |
4 G 70 | 1.545 – 39.2 | 195 | – | 2405 – 3579 | 2/0 |
4 G 95 | 1.665 – 42.3 | 225 | – | 2917 -4340 | 3/0 |
4 G 120 | 1.915 – 48.6 | 260 | – | 3721 – 5536 | 4/0 |
4 G 150 | 2.09 – 53.1 | 290 | – | 4336 – 6452 | 250 MCM |
4 G 185 | 2.33 – 59.2 | 350 | – | 5809 – 8644 | 350 MCM |
4 G240 | 2.5 – 63.7 | 430 | – | 7437 – 11100 | 450 MCM |
Black 3 Conductors
No. of cores x cross section n x mm2 |
Outer Ø inches/mm ±10% |
Current capacity at +30°C Amps |
Copper weight Lbs/Mft – kg/km |
Cable weight approx. Lbs/Mft – kg/km |
AWG no.*) |
3×10+3G2,5 | 0.7 – 17.8 | 55 | – | 401 – 597 | 8 /14 |
3×16+3G4 | 0.785 – 19.9 | 75 | – | 554 – 824 | 6 /12 |
3×25+3G4 | 0.975 – 24.8 | 95 | – | 809 – 1204 | 4 / 12 |
3×35+3G6 | 1.105 – 28.1 | 130 | – | 1147 – 1707 | 2 / 10 |
3×50+3G10 | 1.235 – 31.4 | 145 | – | 1471 – 2189 | 1 / 8 |
3×70+3G10 | 1.42 – 36.1 | 195 | – | 2032 – 3024 | 2/0 / 8 |
3×95+3G16 | 1.53 – 38.9 | 225 | – | 2521 – 3751 | 3/0 / 6 |
3×120+3G16 | 1.76 – 44.7 | 260 | – | 3139 – 4671 | 4/0 / 6 |
3×150+3G16 | 1.915 – 48.6 | 290 | – | 3596 – 53 51 | 250 MCM / 6 |
3×185+3G25 | 2.13 – 54.1 | 350 | – | 4873 – 7521 | 350 MCM / 6 |
3×240+3G35 | 2.26 – 57.3 | 430 | – | 6378 – 9520 | 450 MCM / 2 |