The MS450 manual motor starters covers the range from 15 kW (400 V AC) / 32 A to 22 kW (400 V AC) / 50 A in a width of 55 mm. The MS495 is for the protection of bigger motors up to 55 kW (400 V) / 100 A in a width of 75 mm.
Manual motor starters (MMS) are protection devices for the main circuit. They combine motor control and protection in a single device. MMS are used mainly to switch motors manually ON/OFF and protect them and the installation fuse less against short-circuit, overload and phase failures. Fuse less protection with a manual motor starter saves costs, space and ensures a quick reaction under short-circuit condition, by switching off the motor within milliseconds.
Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three and single-phase applications. The handle is lockable to protect against unauthorised changes. Auxiliary contacts, signalling contacts, undervoltage releases, shunt trips, three-phase busbars, power in-feed blocks are available as accessory.
Rated operational power 400 V |
Setting range | Short-circuit breaking capacity ICS at 400 V AC |
Rated instantaneous short circuit current setting li |
Type | Order code |
Weight (1 pce) |
kW | A | kA | A | kg | ||
MS450 manual motor starter | ||||||
15.8 | 28.0 … 40.0 | 25 | 520.00 | MS450-40 | 1SAM450000R1005 | 1.047 |
22 | 36.0 … 45.0 | 25 | 585.00 | MS450-45 | 1SAM450000R1006 | 1.039 |
22 | 40.0 … 50.0 | 25 | 650.00 | MS450-50 | 1SAM450000R1007 | 1.027 |
MS495 manual motor starter | ||||||
30 | 45.0 … 63.0 | 25 | 819.00 | MS495-63 | 1SAM550000R1007 | 2.247 |
37 | 57.0 … 75.0 | 25 | 975.00 | MS495-75 | 1SAM550000R1008 | 2.253 |
45 | 70.0 … 90.0 | 25 | 1170.00 | MS495-90 | 1SAM550000R1009 | 2.280 |
55 | 80.0 … 100.0 | 25 | 1235.00 | MS495-100 | 1SAM550000R1010 | 2.295 |
Technical Data
Type | MS450, MS495, MS497 |
Standards | IEC/EN 60947-2, IEC/EN 60947-4-1, IEC/EN 60947-1 |
Rated operational voltage Ue | 690 V AC / 450 V DC |
Rated frequency | 50/60 Hz |
Trip class | 10 |
Number of poles | 3 |
Duty time | 100 % |
Rated impulse withstand voltage Uimp | 6 kV |
Rated insulation voltage Ui | 690 V AC |
Short-circuit breaking capacity and back-up fuses
lCS Rated service short-circuit breaking capacity
lCU Rated ultimate short-circuit breaking capacity
ICC Prospective short-circuit current at installation location
Type | 240 V AC | 400 V AC | 440 V AC | 500 V AC | 690 V AC | ||||||||||
ICS kA |
ICU kA |
gG, aM A |
ICS kA |
ICU kA |
gG, aM A |
ICS kA |
ICU kA |
gG, aM A |
ICS kA |
ICU kA |
gG, aM A |
ICS kA |
ICS kA |
gG, aM A |
|
Short-circuit protection MS450 | |||||||||||||||
MS450-40 |
No back-up fuse required up to ICC = 100 kA |
25 | 50 | 160 | 15 | 50 | 125 | 5 | 10 | 100 | 2 | 4 | 63 | ||
MS450-45 | 25 | 50 | 160 | 15 | 50 | 125 | 5 | 10 | 100 | 2 | 4 | 63 | |||
MS450-50 | 25 | 50 | 160 | 15 | 50 | 125 | 5 | 10 | 100 | 2 | 4 | 80 | |||
MS450: No need for back-up fuse in networks with a prospective current of up to 50 kA at 400 V. With an approbiate 160 A type gG fuse the device can be used in a network with a prospective current of up to 100 kA. |
|||||||||||||||
Short-circuit protection MS495 | |||||||||||||||
MS495-40 | No back-up fuse required up to ICC = 100 kA | 25 | 50 | 125 | 20 | 50 | 125 | 6 | 12 | 125 | 3 | 6 | 63 | ||
MS495-50 | 25 | 50 | 125 | 20 | 50 | 125 | 6 | 12 | 125 | 3 | 6 | 80 | |||
MS495-63 | 25 | 50 | 160 | 20 | 50 | 160 | 6 | 12 | 160 | 3 | 6 | 80 | |||
MS495-75 | 25 | 50 | 160 | 20 | 50 | 160 | 6 | 8 | 160 | 3 | 5 | 100 | |||
MS495-90 | 25 | 50 | 160 | 20 | 50 | 160 | 6 | 8 | 160 | 3 | 5 | 125 | |||
MS495-100 | 25 | 50 | 160 | 20 | 50 | 160 | 6 | 8 | 160 | 3 | 5 | 125 | |||
MS495-40: No need for back-up fuse in networks with a prospective current of up to 50 kA at 400 V. With an approbiate 125 A type gG fuse the device can be used in a network with a prospective current of up to 100 kA. MS495-100: No need for back-up fuse in networks with a prospective current of up to 50 kA at 400 V. With an appropriate 160 A type gG fuse the device can be used in a network with a prospective current of up to 100 kA. |
General Technical Data
Type | MS450 | MS495 | ||
Pollution degree | 3 | |||
Phase loss sensitive | Yes | |||
Ambient air temperature | ||||
Operation | Open – compensated without derating | -20 … +60 °C | ||
Open | -20 … +70 °C | |||
Enclosed | -20 … +35 °C | |||
Storage | -50 … +80 °C | |||
Ambient air temperature compensation | Continuous | |||
Maximum operating altitude permissible | 2000 m | |||
Resistance to shock acc. to IEC 60068-2-27 | 25 g / 11 ms | – | ||
Resistance to vibrations acc. to IEC 60068-2-6 | 2 g / 5-150 Hz | |||
Mounting position | Position 1-6 (optional for single mounting) | |||
Mounting | DIN-rail 35 mm (EN 60715) | DIN-rail 15 mm / 75 mm (EN 60715) | ||
Minimum distance to other units same type | Horizontal | 0 mm | 0 mm | |
Vertical – up to 240 V | – | 50 mm | ||
Vertical – up to 440 V | – | 70 mm | ||
Vertical – up to 500 V | – | 110 mm | ||
Vertical – up to 690 V | – | 150 mm | ||
Vertical | 50 mm | – | ||
Minimum distance to electrical conductive board | Horizontal | 10 mm | – | |
Horizontal – up to 500 V | – | 10 mm | ||
Horizontal – up to 690 V | – | 30 mm | ||
Vertical – up to 240 V | – | 50 mm | ||
Vertical – up to 440 V | – | 70 mm | ||
Vertical – up to 500 V | – | 110 mm | ||
Vertical – up to 690 V | – | 150 mm | ||
Vertical | 50 mm | – | ||
Degree of protection | Enclosure / terminals | IP20 |