With Thermal and Electromagnetic Protection
Application
- Short Circuit Protection
- Overload Protection
- Trip class 10
- Phase loss sensitivity
- ON/OFF switching functionality
- Disconnecting feature
- Suitable for three-and single phase applications
Description
- 45 mm width
- Lockable handle
- Clear position of hte handle ON/OFF/TRIP
- Magnetic tripping optically signalled in the front
- One range of common accessories for MS116 & MS132
Ordering Details
Rated Power 400 V AC-3 | Setting Ranges | Type | Order Code | Short-Circuit breaking Ics at 400 V AC |
Rated Instantaneous short circuit current setting |
kW | A … A | kA | A | ||
0.03 | 0.10 … 0.16 | MS132-0.16 | 1SAM 350 000 R1001 | 100 | 1.25 … 1.87 |
0.06 | 0.16 … 0.25 | MS132-0.25 | 1SAM 350 000 R1002 | 100 | 1.95 … 2.92 |
0.09 | 0.25 … 0.40 | MS132-0.4 | 1SAM 350 000 R1003 | 100 | 3.12 … 4.68 |
0.12 | 0.40 … 0.63 | MS132-0.63 | 1SAM 350 000 R1004 | 100 | 4.91 … 7.37 |
0.25 | 0.63 … 1.00 | MS132-1.0 | 1SAM 350 000 R1005 | 100 | 9.20 … 13.8 |
0.55 | 1.00 … 1.60 | MS132-1.6 | 1SAM 350 000 R1006 | 100 | 14.7 … 22.1 |
0.75 | 1.60 … 2.50 | MS132-2.5 | 1SAM 350 000 R1007 | 100 | 23.0 … 34.5 |
1.5 | 2.50 … 4.00 | MS132-4.0 | 1SAM 350 000 R1008 | 100 | 40.0 … 60.0 |
2.2 | 4.00 … 6.30 | MS132-6.3 | 1SAM 350 000 R1009 | 100 | 63.0 … 94.5 |
4 | 6.30 … 10.0 | MS132-10 | 1SAM 350 000 R1010 | 100 | 120 … 180 |
5.5 | 8.00 … 12.0 | MS132-12 | 1SAM 350 000 R1012 | 100 | 144 … 216 |
7.5 | 10.0 … 16.0 | MS132-16 | 1SAM 350 000 R1011 | 100 | 192 … 288 |
9 | 16.0 … 20.0 | MS132-20 | 1SAM 350 000 R1013 | 100 | 240 … 360 |
12.5 | 20.0 … 25.0 | MS132-25 | 1SAM 350 000 R1014 | 50 | 300 … 450 |
15 | 25.0 … 32.0 | MS132-32 | 1SAM 350 000 R1015 | 25 | 384 … 576 |
Technical Data
MS132 | |||||||
Manual Motor Starter Types | up to 10 A | up to 16 A | up to 32 A | ||||
Standards | Conformity to standards | IEC/EN60947-1, IEC/EN60947-4-1, UL 508, CSA C22.2 No. 14 | |||||
Phase loss sensitivity | (acc. to IEC/EN 60947-4-1) | Yes | |||||
Disconnecting feature | (acc. to IEC/EN 60947-2) | Yes | |||||
General Data | Mounting Position | Position 1-6 | |||||
Degree of protection | (acc. to IEC 60947-1) | IP 20 | |||||
Mechancial durability | 100000 cycles | ||||||
Electrical durability | 50000 cycles | ||||||
Utilisation category | A | ||||||
IEC Main Circuit | Rated operational voltage Ue | AC | 690 V AC | ||||
(acc. to IEC / EN 60947-1) | DC | 250 V DC | |||||
Rated operational current Ie | up to 10 A | up to 16 A | up to 32 A | ||||
Rated operational current DC-5 Ie | |||||||
3 conducting paths in series up to 250 V | see”rated operational current” | ||||||
Rated service short-circuit breaking capacity DC Ics | 10 kA | ||||||
3 conducting paths in series up to 250 V | |||||||
Rated frequency | DC, 50 / 60 Hz | ||||||
Trip class | 10 (10A for MS132-0.16) | 10 | 10 | ||||
Isolation Data | Rated impulse withstand voltage Uimp | 6 kV | |||||
(acc. to IEC/EN 60947-1) | Rated insulation Ui | 690 V | |||||
Environmental data | Ambient air temperature | ||||||
Operation | Open – compensated | -25 … +60 oC | |||||
Open | -25 … + 70oC | ||||||
Enclosed (IB132) | 0 … +40oC | ||||||
Storage | -50 … +80oC | ||||||
Vibration | (acc. to IEC/EN 60068-2-6) | 5g / 3-150 Hz | |||||
Shock | (acc. to IEC/EN 60068-2-27) | 25 g / 11ms | |||||
Connecting Capacity | Rigid | 1 or 2 x | 1 … 4 mm2 | 1 … 4 mm2 | 2.5 … 6 mm2 | ||
Flexible with ferrule | 1 or 2 x | 0.72 … 2.5mm2 | 0.75 … 2.5mm2 | 1 … 6 mm2 | |||
Flexible without ferrule | 1 or 2 x | 0.75 … 2.5mm2 | 0.75 … 2.5mm2 | 1 … 6 mm2 | |||
Stripping Length | 9mm | 10mm | 10mm | ||||
Tightening Torque | 0.8 … 1.2 Nm | 1.5 Nm | 2.0 Nm | ||||
UL/CSA | |||||||
Main Circuit | Max. Operational Voltage | 600 V AC | |||||
Short Circuit Rating | 480 V AC | 30 kA | |||||
600 V AC | 18 kA | ||||||
Connecting Capacity | Stranded | 1 or 2 x | AWG 16 … 12 | AWG 16 … 12 | AWG 12 … 8 | ||
Flexible with ferrule | 1 or 2 x | AWG 16 … 12 | AWG 16 … 12 | AWG 12 … 8 | |||
Stripping length | 9mm | 10mm | 10mm | ||||
Tightening torque | 10 … 12 lb.in | 14 lb.in | 18 lb.in |