MCB´s protect installations against overload and short-circuit, warranting reliability and safety for operations.
The System pro M compact S 200 series satisfies most common requirements in terms of MCB´s, allowing the usage of them for domestic, industrial and commercial applications. All the MCB´s comply to IEC/EN 60898 and IEC/EN 60947-2 Standards.
Click to view the ordering information for the S 200 MCB and the S 200 M MCB or scroll down for more technical product information.
Miniature Circuit Breakers (MCBs)
- For domestic / residential installations in emerging markets: typical breaking capacities 3 / 4.5 / 6 kA
- Compact Home SH 200 T, SH 200 L, SH 200
- For domestic or small commercial installations: up to 10 kA breaking capacity
- specials S440, S950/970
- proM compact S200, S200 M
- For industrial installations up to 25 kA breaking capacity and specials
- proM compact S200, S200M, S200P, S200U, S200UP
- specials S280UC, S290
- Special, selective, back-up MCB’s for for utilities, with high breaking capacity (25 kA) and full selectivity to downstream breakers, range S 700
- For commercial and industrial applications with high breaking capacities and special features / accessories, ranges S200P, 290, S500, S610, S220, S800
S 200 and S 200 M MCB Features
- Clear contact position indication in red/green (“real CPI”)
- Unique, patented twin terminal with captive screws and an increased opening for cables up to max. 35 mm2, finger-proof (IP20)
- Busbar slot in the back for best visibility during installation
- High performance at an increased rated voltage for marine and industrial applications: 10 kA/15 kA at Ue = 440 V AC acc. to IEC/EN 60947-2
- Individual product identification code
- Approved acc. to IEC/EN 60898-1, IEC/EN 60947-2 and
- UL 1077/CSA 22.2 No. 235 for global use
System Pro M S 200 / S 200 M Compact General Features and Breaking Capacities
S 200 | S 200 M | ||||
Characteristics | B,C,D,K,Z | B,C,D,K,Z | |||
Rated current | (A) | 0.5 ≤ ln ≥ 63 | 0.5 ≤ ln ≥ 63 | ||
Breaking Capacity | kA | ||||
Reference Standard | Nr. Poles | Ue(V) | |||
IEC 23-3/EN 60898 | lcn | 230/400 | 6 | 10 | |
IEC/EN 60947-2 | Icu | 1, 1P+N | 133 | 20 | 25* |
Alternating current | 230 | 10 | 15* | ||
2, 3, 4 | 230 | 20 | 25* | ||
400 | 10 | 15* | |||
2, 3, 4 | 500 | ||||
690 | |||||
Ics | 1, 1P+N | 133 | 15 | 18.7* | |
230 | 7.5 | 11.2* | |||
2, 3, 4 | 230 | 15** | |||
400 | 7.5 | 11.2* | |||
2, 3, 4 | 500 | ||||
690 | |||||
IEC / EN 60947-2 | lcu | 1, 1P+N | 24 | 20 | |
Direct Current | 60 | 10 | |||
T=I/R≤5ms for all | 125 | ||||
series, | 250 | ||||
except S280 UC and | 2 | 48 | 20 | ||
S800S-US | 125 | 10 | |||
where T=I/R<15ms | 250 | ||||
500 | |||||
600 | |||||
800 | |||||
Ics | 1, 1P+N | 24 | 20 | ||
60 | 10 | 10 | |||
125 | |||||
250 | |||||
2 | 48 | 20 | |||
125 | 10 | 10 | |||
250 | |||||
500 | |||||
600 | |||||
800 | |||||
UL 1077 / C22.2 | Int. | 1, 1P+N | 120 | 10 | |
No 235 | cap. | 277 | 6 | ||
2, 3, 4 | 240 | 10 | |||
480 Y/277 | 6 | ||||
UL 1077 / C22.2 | Int. | 1, 1P+N | 60 | 10 | |
No 235 Direct current | cap. | 2, 3, 4 | 125 | 10 | |
UL 489 / C22.2 | Int. | 1 | 240 | ||
No 5 | cap. | 277 | |||
Alternating current | 2, 3, 4 | 240 | |||
480 Y/277 |
* < 50A
**Only up to 40A; 10kA up to 50/63A
ABB S 200 / S 200 M MCB Technical Data
S 200 | S 200 M | |
General Data |
||
Standards | IEC/EN 60898-1, IEC/EN 60947-2UL 1077 | IEC/EN 60898-1, IEC/EN 60947-2UL 1077, CSA 22.2 No. 235 |
Poles | 1P, 2P, 3P, 4P, 1P+N, 3P+N | |
Tripping Characteristics | B, C, D, K, Z | |
Rated current In | 0.5 up to 63 A | |
Rated frequency | 50/60 Hz | |
Rated insulation voltage Ui | 250 V AC (phase to ground), 500 V AC (phase to phase) | |
Overvoltage Category | III | |
Pollution Degree | 3 | |
IEC/EN 60898-1 |
||
Rated operational voltage Un | 1P: 230/400 V AC; 1P+N: 230 V AC; 2P, 3P, 4P: 400 V AC; 3P+N: 400 V AC | |
Max. power frequency recovery voltage Umax | 1P: 253 V AC; 1P+N: 253 V AC; 2P, 3P, 4P: 440 V AC; 3P+N: 440 V AC; 1P: 72 V DC; 2P: 125 V DC | |
Min. operating voltage | 12 V AC, 12 V DC | |
Rated short-circuit capacity Icn | 6 kA | 10 kA |
Energy limiting class (B, C up to 40 A) | 3 | |
Rated impulse withstand voltage Uimp (1.2/50 µs) | 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m) | |
Dielectric test voltage | 2.0 kV (50/60 Hz, 1 min) | |
Reference temperature for tripping characteristics | B, C, D: 30 °C | |
Electrical endurance | In < 32 A: 20,000 ops. (AC), 1,000 ops. (DC); one cycle 2 s – ON, 13 s – OFF | |
In ≥ 32 A: 10,000 ops. (AC), 1,000 ops. (DC); one cycle 2 s – ON, 28 s – OFF | ||
UL/CSA |
||
Rated voltage | 1P: 277 V AC, 60 V DC 2…4P: 480 Y/277 V AC, 110 V DC | 1P: 277 V AC, 60 V DC2…4P: 480 Y/277 V AC, 125 V DC |
Rated interrupting capacity | 6 kA (AC), 10 kA (DC) | |
Application | Suppl. prot. for general use. Application Codes: TC2, OL0, SC: U1 | |
Electrical endurance | 6,000 ops. (AC), 6,000 ops. (DC); one cycle 1 s – ON, 9 s – OFF | |
Mechanical data |
||
Housing | Insulation group II, RAL 7035 | Insulation group I, RAL 7035 |
Toggle | Insulation group II, black, sealable | |
Contact position indication | Marking on toggle (I ON/0 OFF), Real CPI (red ON/green OFF) | |
Protection degree acc. to EN 60529 | IP201), IP40 in enclosure with cover | |
Mechanical endurance | 20,000 ops. | |
Shock resistance acc. to IEC/EN 60068-2-27 | 25 g, 2 shocks, 13 ms | |
Vibration resistance acc. to IEC/EN 60068-2-6 | 5 g, 20 cycles at 5…150…5 Hz with load 0.8 In | |
Environmental conditions acc. to IEC/EN 60068-2-30 | 28 cycles with 55 °C/90-96 % and 25 °C/95-100 % | |
Ambient temperature | -25 … +55 °C | |
Storage temperature | -40 … +70 °C | |
Installation |
||
Terminal | Failsafe bi-directional cylinder-lift terminal | |
Cross-section of conductors (top/bottom) | solid, stranded: 35 mm2 / 35 mm2flexible: 25 mm2 / 25 mm2 | |
14 – 4 AWG 3) | ||
Cross-section of busbars (top/bottom) | 10 mm2 / 10 mm2 | |
14 – 8 AWG2) | ||
Torque | 2.8 Nm | |
18 in-Ibs. | ||
Screwdriver | No. 2 Pozidrive | |
Mounting | On DIN rail 35 mm acc. to EN 60715 by fast clip | |
Mounting position | any | |
Supply | optional | |
Dimensions and weight |
||
Mounting dimensions acc. to DIN 43880 | Mounting dimension 1 | |
Pole dimensions (H x D x W) | 88 x 69 x 17.5 | |
Pole weight | approx. 115 g | |
Combination with auxiliary elements |
||
Auxiliary contact | Yes | |
Signal/auxiliary contact | Yes | |
Shunt trip | Yes | |
Undervoltage release | Yes | |
Motor Operating Device | Yes |
1) Also fulfilling the requirements acc. to the protection degree IPXXB
2) AWG 18 – 8 acc. to UL 486A – 486B
3) AWG 18 – 4 acc. to UL 486A – 486B
Click to view the ordering information for the S 200 MCB and the S 200 M MCB