Special needs require special features and performance:
FC 301 A1* | FC301 | FC302 | |
Power range 200 -240 V [kW] | 0.25-1.5 | 0.25-45 | 0.37 – 45 |
Power range 380- (480) 500 [kW] | 0.37 – 1.5 | 0.37 – 45 | 0.37 – 1.1 M |
Power range 550 -600 V [kWI | – | – | 0.75 – 7.5 |
Power range 525 -690 V [kWI | – | – | 11-1.2 M |
Amb. temp’C Avg.24 hours (IP 21) w/o de-rating | 45 | 45 | 45 |
Ambient temp’C max (IP21) w/o de-rating | 50 | 50 | 50 |
Ambient temp’C max with de-rating | 55 | 55 | 55 |
IP 21/NEMA typel/1P 5SINEMA type12 | |||
IP66/NEMAtype4x | – | ||
Smart Logic Control | |||
Logic Rule Control | |||
Safe Stop input function approved | – | ||
Local Control Panel numerical or graphical | |||
Info/Help function Personal menu (macro) | |||
Regional settings (US mode) | |||
Language settings | |||
Change made restore previous setting | |||
Password protection | |||
Analogue input | 0 to +10V | 0 to +10V | -10 to +10V |
Digital inputs | 5 | 5 | 6 |
Digital transistor outputs ‘1 | 1 | 1 | |
Relay outputs | 1 | 1 | 2 |
Analogue output resolution | 12 bit | 12 bit | 12 bit |
PC connection: RS 485 and USB | |||
Default motor data | |||
Permanent Magnet Motor algorithm | – | – | |
Process PID control | |||
Precise Start/Stop | |||
Preset references | 8 | 8 | 8 |
Digipotmeter | |||
Ramp functions: linear and S-ramps | |||
Profibus, DeviceNet, CANOpen | |||
ProfiSafe | – | – | |
Interface options: | |||
Extended input/outputs MCB 101 | |||
Encoders option MCB 102 | |||
Resolver option MCB 103 | |||
Relay option MCB 1OS | |||
Safe PLC interface MCB 108 | – | ||
Motion Control Options: MCO 305 | – | ||
External 24 Vback-up option MCB 107 | – | ||
Cable length -screened/unscreened | 25/50m | 50/75m | 150/300 m |
RFI EN55011 cI A2 (Industry) | <5 m | <5m | <5m |
RFI EN55011 cI Al (Industry) | <25 M | <50m | <150 m |
RFI EN55011 cI B(Domestic) | 2.5 m | <10 m | <50 m |
Voltage Vector Control WC+ | |||
FluxVector Control | – | – | |
Automatic Energy Optimizing (AOE) | – | – | |
Controlled ramp down | – | – | |
Flying start -catch spinning motor | |||
Variable switching frequency 1 -16 kHz 2) | |||
Over Voltage Control | |||
Fan replaceable |
*Smallest cabinet size
1. Converting digital inputs
2. Power size dependent
Click here for a Danfoss FC301 / FC302 Overview Brochure.