The Prysmian FP100 is the original fire resistant single core cable for use in steel conduit or trunking.
Use FP100 when upgrading existing steel conduit systems to current specification and also for new build projects featuring metallic trunking. It is ideal for emergency lighting, fire detection and fire alarm circuits for systems that do not require twisted pairs or a built-in metallic screen.
Suitable for use as part of a ‘standard’ or ‘enhanced’ fire resistant cable system, FP100 can help solve the installation issues when surface or void installation is not an option
FP100 Cable Features
- Fire Resistant Conduit Wiring Cable
- 450/750V
- BS6387 Category C,W & Z*
- BS EN 50200 PH30, PH60 and PH120*
- BS EN 50200+Annex E*
- BS8434-2*
- Use in steel conduit to achieve fire rating
- LPCB Approved
- Low smoke, zero halogen, flame retardant
Type Approval Certificates : | LPCB - Loss Prevention Certification Board |
|
FSD : Fire Services Department |
Conductor : | Stranded bare copper class 2 IEC 60228 |
Primary Insulation : | Mineral ceramic (Mica / Glass) fire resistant tape |
Secondary Insulation : | 90oC high performance cross linked mineral filled insulation |
Marking |
1 x S mm2 - 0.6 / 1kVMX 331 IEC 60331, BS 6387 cat. CWZ LPCB 253d / 01 |
Core Identification : | Colours : red, black, blue, yellow, white, green / yellow |
Fire resistant : | IEC 60331, BS 6387 CWZ; SS 299 CWZ |
Fire retardant : | IEC 60332 Part 3 & 1; EN 50265 1 & 2.1 |
Low Smoke : | IEC 61034; NFC 32-073; EN 50268; BS 7622 |
Halogen Free : | IEC 60754; NFC 32-074; EN 50267; BS 6425 |
Low corrosivity | IEC 60754; NFC 32-074; EN 50267; BS 6425 |
Temperature : | -20 + 60oC |
Prysmian FP100 Ordering Information
Nominal Cross Sectional Area | Approximate Overall Diameter | Approximate cable weight | Maximum conductor resistance at 20oC | Short Circuit rating (1 sec) | Current rating DC or single phase AC | Current rating Three phase AC | Volt drop DC | Volt drop Single phase AC | Volt drop Three phase AC |
mm2 | mm | Kg / Km | ohms / km | Amps | Amps | Amps | mV / A/ m | mV / A/ m | mV/A/m |
1.5* | 3.5 | 26 | 12.1 | 215 | 22 | 19 | 31 | 31 | 27 |
2.5* | 4.1 | 38 | 7.41 | 360 | 30 | 26 | 19 | 19 | 16 |
4* | 4.6 | 54 | 4.61 | 570 | 40 | 35 | 12 | 12 | 10 |
6* | 5.2 | 75 | 3.08 | 860 | 51 | 45 | 7.9 | 7.9 | 6.8 |
10* | 6.6 | 120 | 1.83 | 1425 | 71 | 63 | 4.7 | 4.7 | 4 |
16 | 7.7 | 180 | 1.15 | 2275 | 95 | 85 | 2.9 | 2.9 | 2.5 |
25 | 9.0 | 270 | 0.727 | 3375 | 126 | 111 | 1.85 | 1.9 | 1.65 |
35 | 10.0 | 360 | 0.524 | 5000 | 156 | 138 | 1.35 | 1.35 | 1.15 |
50 | 11.7 | 490 | 0.387 | 7150 | 189 | 168 | 0.99 | 1.05 | 0.9 |
70 | 13.2 | 680 | 0.268 | 10000 | 240 | 214 | 0.68 | 0.75 | 0.65 |
95 | 15.3 | 940 | 0.193 | 13575 | 290 | 259 | 0.49 | 0.58 | 0.5 |
120 | 16.8 | 1160 | 0.153 | 17150 | 336 | 299 | 0.39 | 0.48 | 0.42 |
150 | 18.7 | 1440 | 0.124 | 21450 | 375 | 328 | 0.32 | 0.43 | 0.37 |
185 | 20.8 | 1800 | 0.0991 | 26450 | 426 | 370 | 0.25 | 0.37 | 0.32 |
240 | 23.5 | 2350 | 0.0754 | 34325 | 500 | 433 | 0.19 | 0.33 | 0.29 |
300 | 27.3 | 3000 | 0.0601 | 42925 | 573 | 493 | 0.155 | 0.31 | 0.27 |
400 | 32.5 | 3970 | 0.0470 | 57225 | 683 | 584 | 0.120 | 0.29 | 0.25 |
500 | 36.0 | 4980 | 0.0366 | 71525 | 783 | 666 | 0.093 | 0.28 | 0.24 |
630 | 40.0 | 6340 | 0.0283 | 90125 | 900 | 764 | 0.072 | 0.27 | 0.23 |