BS6622 Cu/XLPE/CTS/PVC/AWA/PVC 6.36/11kV - 1 core
Cu/XLPE/CTS/PVC/SWA/PVC 11kV medium voltage power cable may be used for power networks, in fixed installation outdoors in cable ducts or directly in the ground. The cable consists of a Class 2 stranded copper conductor, semi conductive conductor screen, XLPE insulation, semi conducting layer with a plain copper tape screen, PVC bedding, Aluminium Wire Armour and red PVC outer sheath. 6350/11000 volts to BS6622 and IEC 60502-2, flame retardant to IEC 60332-1.
Construction Characteristics
Electrical Characteristics
Usage Characteristics
1 Core: Brown
Part Number |
Cross Section |
Stranding |
Approx Weight |
Approx Overall Diameter |
Gland Size |
Single Cleat |
Nom. Max. DC-resist conductor 20°C |
Current rating laid direct |
(mm²) |
(mm) |
KG/KM |
(mm) |
(mm) |
|
(Ohm/km) |
(Amp) |
11KVPVC1X50 |
1 x 50 |
19/1.78 |
1210 |
28.5 |
32 |
1.2 |
0.387 |
221 |
11KVPVC1X70 |
1 x 70 |
19/2.14 |
1500 |
30.5 |
32 |
1.2 |
0.268 |
270 |
11KVPVC1X95 |
1 x 95 |
19/2.52 |
1700 |
32.4 |
32 |
1.4 |
0.193 |
321 |
11KVPVC1X120 |
1 x 120 |
37/2.03 |
2105 |
34.2 |
40 |
1.4 |
0.153 |
363 |
11KVPVC1X150 |
1 x 150 |
37/2.25 |
2505 |
36.4 |
40 |
1.6 |
0.124 |
410 |
11KVPVC1X185 |
1 x 185 |
37/2.52 |
2900 |
37.7 |
40 |
1.6 |
0.0991 |
455 |
11KVPVC1X240 |
1 x 240 |
61/2.25 |
3532 |
40.6 |
50s |
1.6 |
0.0754 |
520 |
11KVPVC1X300 |
1 x 300 |
61/2.52 |
4230 |
42.7 |
50s |
1.8 |
0.0601 |
580 |
11KVPVC1X400 |
1 x 400 |
61/2.85 |
5145 |
46.4 |
50s |
2.0 |
0.0470 |
650 |
11KVPVC1X500 |
1 x 500 |
61/3.20 |
6450 |
51.0 |
50 |
2.0 |
0.0366 |
710 |
11KVPVC1X630 |
1 x 630 |
127/2.52 |
7950 |
59.9 |
63s |
R9 |
0.0283 |
761 |
11KVPVC1X800 |
1 x 800 |
127/2.85 |
9720 |
60.0 |
63 |
R10 |
0.0221 |
812 |
11KVPVC1X1000 |
1 x 1000 |
127/3.2 |
11860 |
64.0 |
75s |
R11 |
0.0176 |
868 |