Voltage Drop (per ampere per metre): | Conductor Operating Temperature: 70oC | ||
Conductor cross-sectional area | Two-core cable d.c. | Two-core cable single-phase a.c. | Three- or four-core cable, three-phase a.c. |
1 | 2 | 3 | 4 |
(mm2) | (mV/A/m) | (mV/A/m) | (mV/A/m) |
1 | 44 | 44 | 38 |
1.5 | 29 | 29 | 25 |
2.5 | 18 | 18 | 15 |
4 | 11 | 11 | 9.5 |
6 | 7.3 | 7.3 | 6.4 |
10 | 4.4 | 4.4 | 3.8 |
16 | 2.8 | 2.8 | 2.4 |
List of Other Technical Tables & Useful Links
- Table 4D1A | Single-core 70°C Thermoplastic Insulated Cables, Non-Armoured, with or without Sheath
- Table 4D2A | Multicore 70°C Thermoplastic Insulated and Thermoplastic Sheathed Cables, Non-Armoured
- Table 4D2B | Voltage Drop (per ampere per metre): Conductor Operating Temperature: 70°C
- Table 4E1A | Current-carrying Capacity Single-Core 90°C Thermosetting Insulated Cables, Non-Armoured, with or without Sheath
- Table 4E1B | Voltage Drop Single-Core 90°C Thermosetting Insulated Cables, Non-Armoured, with or without Sheath
- Table 4E2A | Multi-Core 90°C Thermosetting Insulated Cables and thermoplastic Sheathed Cables, Non-Armoured
- Table 4E2B | Voltage Drop (per ampere per metre): Conductor Operating Temperature: 90°C
- Table 4E3A | Single-Core Armoured 90°C Thermosetting Insulated Cables, Non-Magnetic Armour
- Table 4E3B | Voltage Drop (per ampere per metre):Conductor Operating Temperature: 90°C
- Table 4E4A | Multicore 90°C Thermosetting Insulated Cables
- Table 4E4B | Voltage Drop (per ampere per metre):Conductor Operating Temperature: 90°C
- Table 4F1A | 60°C Thermosetting Insulated Flexible Cables with Sheath, Non-Armoured
- Table 4F1B | 60°C Thermosetting Insulated Flexible Cables
- Table 4F2A | 90°C and 180°C Thermosetting Insulated Flexible Cables with Sheath, Non-Armoured (Copper Conductors)
- Table 4F2B | Voltage Drop (per ampere per metre): Conductor Operating Temperature: 90°C
- Table 4F3A | Flexible Cords, Non-Armoured
- Table 4F3B | Voltage Drop (per ampere per meter): Conductor Operating Temperature: 60°C
- AWG/Metric Conversion
- Stranding Chart
- BS 5308 Colour Codes
- Harmonised Cable Core Colours
- Cable Certifications
- Cable Colours
- DIN 47100 European Colour Codes
- Fire Performance Cable Standards
- Voltage Drop Calculations