RT 5M Capillary Tube

RT Standard

Contact Type: SPDT
Contact material: Silver cadmium oxide
Loads: AC-1 ohmic 10A 400V
AC-3 (motor) 4A 400v
AC-15 (inductive) 3A 400V
Ambient Temperature -50 to 70°c

Type of Charge– with designation letters:
A: Vapour charge – sensor must not be the warmest part.
B: Adsorption charge
C: Partial charge – the sensor must not be the coldest part

OrderCode Type Type of Charge Set.Range°C Adjustable Diff at lowest range °C Adjustable Diff at Highest range °C Max Sensor Temperature°C
017-5016 RT3 A -25 > 15 2.8 > 10 1 > 4 150
017-5055 RT7 B -25 > 15 2 > 10 2.5 > 14 150
017-5101 RT14 B -5 > 30 2 > 8 2 > 10 150
017-5022 RT101 B 25 > 90 2.4 > 10 3.5 > 20 300
017-5050 RT106 C 20 > 90 4 > 20 2 > 7 120
017-5140 RT107 C 70 > 150 6 > 25 1.8 > 8 215
017-5206 ^ RT120 C 120 > 215 7 > 30 1.8 > 9 260
017-5209 RT120 C 120 > 215 7 > 30 1.8 > 9 260
017-5222 RT123 C 150 > 250 6.5 > 30 1.8 > 9 300
017-5229 RT124 C 200 > 300 5 > 25 2.5 > 10 350

^ Thermostats fitted with Neon lamp connected to terminal 4

RT Data Sheet