KP thermostats are single-pole, double-throw (SPDT) temperature operated electric switches.
KP is used for regulation, but can also be seen in safety monitoring
systems. It is here that the electronic mechanism shows its superiority.
KP thermostats are available with vapour charge or with adsorption charge.
Read More
Click for the Danfoss Type KP Thermostat data sheet
Technical Data
Ambient temperature : | -40oC to 65oC (for short periods up to 80oC) |
Enclosure : | IP30; with top cover or protection cap: IP44 |
Electrical connection : | Cable entry for diameters 6 to 14mm |
Contact system : | SPDT |
Contact load : | AC-1 Ohmic : 16A, 440V |
AC-3 (motor) : 16A, 440V | |
AC-14/15 (coil / transformer): 10A, 440V | |
DC-13/14: 12W, 220V |
Code No. | Setting range | Differential | Max. Sensor Temperature(oC) | Capilliary tube length (m) | Type |
060L1126 | 50 to 100 | 5 to 15 | 150 | 2 | KP79 |
060L1125 | 80 to 150 | 7 to 20 | 200 | 2 | KP81 |
060L1183 | 80 to 150 | 7 to 20 | 200 | 3 | KP81 |